Thứ năm, 16/04/2026 | 17:13
Abstract Multi-rated-voltage multi-circuit overhead transmission lines are increasingly used because of their reduced construction costs, and right-of-way requirement. However, using these transmission lines bring along with disadvantages in terms of lightning protection. This paper studies application of line surge arresters to reduce lightning outage rate for four-circuit transmission line with two rated voltage levels of 220 kV and 110 kV built on a single tower. The study utilizes Electro-Geometric Model (EGM) method and EMTP/ATP simulation software. Outage rate in cases of different arrangements of line surge arrester are evaluated and compared. Effect of parameters such as tower footing resistance and tower height are analyzed. Absorbed energy and current through line surge arrester are also determined as basic for selection of suitable line surge arrester Keywords: Transmission line, line surge arrester, outage rate, EMTP/ATP. |
Sự ra đời của Nghị quyết số 57-NQ/TW ngày 22/12/2024 của Bộ Chính trị đã đánh dấu bước ngoặt quan trọng trong tư duy và định hướng phát triển khoa học, công nghệ, đổi mới sáng tạo và chuyển đổi số. Không chỉ mang ý nghĩa chiến lược ở tầm quốc gia, nghị quyết còn mở ra “thời cơ vàng” để các địa phương tận dụng tiềm năng, bứt phá mạnh mẽ, nâng cao năng lực cạnh tranh và hướng tới phát triển bền vững trong bối cảnh kinh tế số và cách mạng công nghiệp 4.0.
16/04/2026